SIPLUS S7-400 interface modules

Получить цену
0,375394104

Обзор

  • To connect distributed I/O via PROFIBUS DP
  • Max. transmission rate 12 Mbit/s
  • Electrically isolated RS-485 interface
  • Connection via 9-pin Sub-D socket
  • One or two PROFIBUS modules can be plugged in for each S7-400 CPU:
    • CPU 414-3/416-3: 1 module
    • CPU 417-4: 2 modules


Notes:

Can only be used with the CPUs 6AG1 416-3XR05-4AB0, 6AG1 416-3ER05-4AB0 and 6AG1 417-4XT05-4AB0.

SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.

Technical documentation on SIPLUS can be found here:
http://www.siemens.de/siplus-extreme

Технические данные

Article number

6AG1964-2AA04-7AB0

SIPLUS S7-400 IF964-DP

Input current

from CPU, max.

150 mA, Current consumption from S7-400 bus: The module uses no current at 24 V, it provides this voltage only at the DP interface. Total current consumption of the components connected to the DP interface, but maximum 150 mA. Current carrying capacity of the isolated 5 V (P5ext) maximum 90 mA, current carrying capacity of the 24 V maximum 150 mA.

Power loss

Power loss, typ.

1 W

Interfaces

PROFIBUS DP

Cable length

  • Cable length, max.

1 200 m, At 9.6 kbit/s: max. 1200 m, at 12 Mbit/s: max. 100 m

1. Interface

Physics

RS 485

Isolated

Yes

Functionality

  • ? PROFIBUS DP master

Yes, Default setting

  • ? PROFIBUS DP slave

Yes

DP master

  • ? Transmission rate, max.

12 Mbit/s

  • ? Number of DP slaves, max.

125, depending on the CPU used

Services

  • PG/OP communication

Yes

  • Equidistance

Yes

  • SYNC/FREEZE

Yes

  • Direct data exchange (slave-to-slave communication)

Yes

Address area

  • Inputs, max.

device-dependent

  • Outputs, max.

device-dependent

User data per DP slave

  • Inputs, max.

244 byte

  • Outputs, max.

244 byte

Communication functions

Number of connections

  • ? overall

device-dependent

Ambient conditions

Ambient temperature during operation

  • ? min.

-25 °C, = Tmin

  • ? max.

70 °C, = Tmax, @ 60°C for UL/ATEX/FM use

Extended ambient conditions

  • ? relative to ambient temperature-atmospheric pressure-installation altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100 %, Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)

Resistance

  • against biologically active substances / conformity with EN 60721-3-3

Yes, Class 3B2 mold, fungus and dry rot spores (with the exception of fauna), Class 3B3 on request

  • against chemically active substances / conformity with EN 60721-3-3

Yes, Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • against mechanically active substances / conformity with EN 60721-3-3

Yes, Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Dimensions

Width

26 mm

Height

54 mm

Depth

130 mm

Weights

Weight, approx.

65 g