SM 422 digital output module

Получить цену
0,489207468

Обзор

  • Digital outputs for the SIMATIC S7-400
  • For connecting solenoid valves, contactors, low-power motors, lamps and motor starters

Область применения

Digital output modules can be used to output digital signals from the control to the process. They are suitable, for example, for connecting solenoid valves, contactors, low-power motors, lamps and motor starters.

Дизайн

Digital output modules are characterized by the following mechanical features:

  • Compact configuration:
    The rugged plastic housing contains:
    • Green LEDs for indicating the signal statuses at the outputs
    • One red LED each to indicate internal and external faults or errors, and to display blown fuses and the absence of the load voltage
    • Labeling strips
  • Simple assembly
  • User-friendly wiring:
    The modules are wired by means of a plug-in front connector.

Функции

Digital output modules convert the internal signal levels of the S7-400 in the external signal levels required for the process.

Технические данные

Article number

6ES7422-1FH00-0AA0

6ES7422-1HH00-0AA0

6ES7422-1BH11-0AA0

6ES7422-1BL00-0AA0

6ES7422-7BL00-0AB0

SM422, 16DO, AC120/230V, 2A

SM422, 16DO, AC5-230V, 5A RELAY

SM422, 16DO, DC24V, 2A,

SIMATIC S7-400, SM 422

SIMATIC S7-400, DIG.OUTPUT MOD.

Supply voltage

Load voltage L+

  • ? Rated value (DC)

60 V

24 V

24 V

24 V

  • ? permissible range, lower limit (DC)

1 V

20.4 V

20.4 V

20.4 V

  • ? permissible range, upper limit (DC)

60 V

28.8 V

28.8 V

28.8 V

Load voltage L1

  • ? Rated value (AC)

230 V, 120/230V AC

230 V

  • ? permissible range, lower limit (AC)

79 V

2 V

  • ? permissible range, upper limit (AC)

264 V

264 V

Input current

from load voltage L+ (without load), max.

1.5 mA

30 mA

30 mA

120 mA

from backplane bus 5 V DC, max.

400 mA

1 A

160 mA

200 mA

200 mA

Power loss

Power loss, typ.

16 W

4.5 W

5 W

4 W

8 W

Digital outputs

Number of digital outputs

16

16, Relays

16

32

32

Limitation of inductive shutdown voltage to

-30 V

-27 V

L+ (-45 V)

Switching capacity of the outputs

  • ? on lamp load, max.

50 W

60 W

10 W

5 W

5 W

Output voltage

  • ? for signal '1', min.

L1 (-18.1 V)

L+ (-0.5 V)

L+ (-0.3 V)

L+ (-0.8 V)

Output current

  • ? for signal '1' rated value

2 A

5 A

2 A

0.5 A

0.5 A

  • ? for signal '1' permissible range, min.

10 mA

5 mA

5 mA

5 mA

  • ? for signal '1' permissible range, max.

2 A

2.4 A

0.6 A

600 A

  • ? for signal '0' residual current, max.

2.6 mA

0.5 mA

0.3 mA

0.5 mA

Switching frequency

  • ? with resistive load, max.

10 Hz

10 Hz

100 Hz

100 Hz

100 Hz

  • ? with inductive load, max.

0.5 Hz

0.1 Hz

0.5 Hz

2 Hz

Total current of the outputs (per group)

all mounting positions

Похожие товары